Sign In | Join Free | My burrillandco.com |
|
Ask Lasest Price | |
Brand Name : | YN |
Model Number : | YN-BFU-610 |
Certification : | CE/ISO |
Price : | reconsideration |
Payment Terms : | L/C, D/A, T/T, Western Union |
Supply Ability : | 10000pcs/month |
Delivery Time : | 7-15 work days |
The BFU terminal hepa filter unit, which uses the latest technology in the United States, is a ceiling unit with a fan inside, used for turbulent flow and laminar flow clean room. BFU fan filter unit is one of the quietest and best-priced units on the market.
FFU is an abbreviation for English, the full name is Fan Filter Units, which means "fan filter unit (unit)". That is, a fan and a filter (HEPA) or Ultra High Efficiency Filter (ULPA) are combined to form a self-powered end purification device. Specifically, it is a self-contained, modular end air supply with filtering efficiency. The fan draws in air from the top of the FFU and filters it through HEPA. The filtered clean air is evenly sent out over the entire wind surface at a wind speed of 0.45 m/s ± 20%.
1), lightweight module structure design, suitable for the
installation of the ceiling keel (T-Grid) system of each
manufacturer;
2), with dual overload protection high-performance motor, high
static pressure, low noise, low energy consumption, can save
operating costs;
3), low noise, the source of scientific motor and wind guiding
structure design, so that the noise level of the product is lower
than similar products;
4), the air is even, the wind pressure spreads evenly to meet the
requirements of the international standard IES-RP-CC002 +/- 20%;
5), low fretting, the total vibration rate is less than 1mm / s,
the amplitude does not exceed 3um;
6), flexible control mode, can be used for single-speed,
three-stage speed regulation, five-stage speed regulation or
stepless speed regulation to adjust air volume and with
operation/abnormal indicator/abnormal dry contact for easy
monitoring;
7), can be customized for a variety of special specifications;
8), pre-filter (G3-G4) and chemical molecular filter can be added
as needed.
9), can install abnormal indoor fault LED lights;
10), can be installed with differential pressure gauge, wind speed
sensor, etc.;
11), can be installed with a small 99 monitoring system or a large
remote central monitoring system.
Model | FFU/BFU-YN920 | FFU/BFU-YN1175 | FFU/BFU-YN1225 | Unit |
Size | 920×615×350 | 1175×575×350 | 1225×615×350 | mm |
plenum chamber materials | Aluminized zinc plate/stainless steel. | Aluminized zinc plate/stainless steel. | Aluminized zinc plate/stainless steel. | |
Air flow | 800 | 1000 | 1200 | m3/h |
Average wind velocity | 0.4/0.45/0.5 | 0.4/0.45/0.5 | /0.4/0.45/0.5 | m/s |
Extemal static pressure | 97(10mmAq) | 97(10mmAq) | 97(10mmAq) | pa |
Hepa filter size | 915×610×69 | 1170×570×69 | 1220×610×69 | mm |
Efficiency | 0.12um@99.99% | 0.12um@99.99% | 0.12um@99.99% | |
Filter initial pressure loss | 180Pa@0.45m/s | 180Pa@0.45m/s | 180Pa@0.45m/s | |
Power | 180Pa@0.45m/s | 180Pa@0.45m/s | 180Pa@0.45m/s | |
Fan vibration coefficient | 0.2-0.5mm/s | 0.2-0.5mm/s | 0.2-0.5mm/s | |
Power dissipation | 123 | 123 | 172 | W |
Weight | 24 | 28 | 31 | Kg |
Noise | 53 | 55 | 55 | dB |
![]() |